Your shopping cart is empty!
The Integra 1630 digital metering system (dms) with user selectable configuration provides high accuracy 0.2% measurement, display and communication of all major electrical and power quality parameters including total harmonic distortion (THD) up to the 31st harmonic. To suit user requirements, the range includes single-phase, three-phase three-wire and three-phase four-wire capability, all selectable at the point of installation.
INPUT. 140-277V L-N 3~ (241-480V L-L 3~), INPUT. 5A CT OPERATED, AUXILIARY. 100-250V AC/DC
Features
- Measurement, display and communication of electrical and power parameters
- High contrast LED or LCD display
- THD measurement and power quality data to 31st harmonic
- True rms and average sensing measurement
- Pulsed, analogue and digital outputs
- Modbus RTU RS485 protocol, Johnson Controls and Lonworks protocol interface options
- Fully programmable VT and CT ratios
Benefits
- Pre-calibrated plug-in options
- Simple menu driven interface
- Remote monitoring
- True three-and four-wire measurement
Click the PDF below to read more about the Crompton Instruments Integra 1630 digital metering system.